operated,function,release,contact,monitoring,contacts,monitored,version,positive

 


E-Stop with Ronis Operated Reset

E-Stop with Ronis Operated Reset
EJ
Monitoring
EK
No monitoring
  • 2 force break positive make NC Safety contacts (uses none of the I/O pins)
  • Monitored version (EK) also has 1NO monitoring contact and this uses 1 output pin
  • With Ronis key operated reset function
  • 40mm button

Twist release after use of the reset key



TUV (EU+USA+Canada)

I/O & Safety Circuits

Images

E-Stop with Ronis Operated Reset
E-Stop with Ronis Operated Reset




Safety Data

Standards EN 60947-1:2007 (Low-voltage switchgear and control gear), EN60975-5-1:2004, EN62061:2005, EN/ISO13849-1:2008, EN50178:1997, EN60204-1:2006, EN50295:1999, GS-ET-19:04/2004
Certifications CE marked for all applicable directives
Category Cat. 4, PLe (EN/ISO 13849-1) and SIL3 (EN/IEC 62061)
Functional safety data* B10d 500.000
MTTfd High > 385 years (590 years)
CCF  
DC High 99% (with correct monitoring of both channels and including the opposite-mode monitoring switch)
PFHd [1/h] 5,90E-10

* eGard modules need to be constructed as a complete assembly to reach stated values

Downloads and drawings (Login required)

Installation manual
Datasheet EJ, EK
 

Login

 
  Not a registered visitor? Click here.
Personal information