connecting,address,outputs,circuits,controls,addresses

 


AS-Interface Connectors

AS-Interface Connectors
BA
AS-I control & safety (4I & 4O)
BH
AS-I safety only
BG
AS-I control only (4I & 4O)

 

BA 4 pin M12 base for connecting dual safety circuits and up to 4 inputs and up to 4 outputs (uses two addresses)
BH 4 pin M12 base for connecting dual safety circuits only (uses one address)
BG 4 pin M12 base for connecting controls only up to 4 inputs and up to 4 outputs (uses one address)

 



AS-interface TUV (EU+USA+Canada)

Images

AS-Interface Connectors
AS-Interface Connectors




Safety Data

Standards EN 60947-1:2007 (Low-voltage switchgear and control gear), EN60975-5-1:2004, EN62061:2005, EN/ISO13849-1:2008, EN50178:1997, EN60204-1:2006, EN50295:1999, GS-ET-19:04/2004
Certifications CE marked for all applicable directives
Category Cat. 4, PLe (EN/ISO 13849-1) and SIL3 (EN/IEC 62061)
Functional safety data* B10d 5.000.000
MTTfd High > 385 years (590 years)
CCF  
DC High 99% (with correct monitoring of both channels and including the opposite-mode monitoring switch)
PFHd [1/h] 5,90E-10

* eGard modules need to be constructed as a complete assembly to reach stated values

Downloads and drawings (Login required)

Datasheet BA, BG, BH
Installation manual
 
2D drawing BA - BH - BG